DEHN GUARD SURGE ARRESTER DG M TT 2P 275 - A.C. SINGLE PHASE - 952110

DEHN GUARD SCARICATORE DG M TT 2P 275 - C.A. MONOFASE - 952110 View larger

SCARICATORE DG M TT 952110

New

DEHN GUARD DG M TT 2P 275 surge arrester - A.C. SINGLE PHASE - 952110, lightning current arrester, coordinated SPD Type 1

More details

IN STOCK

83,60 €

For quick informations

WhatsApp+39 3703419348

Add to my wishlist

More info

  • Complete unit, ready for wiring, consisting of a base part plus plug-in protection modules
  • High discharge capacity due to powerful zinc oxide varistors and spark gaps 
  • High reliability thanks to the "Thermo Dynamic Control” controller.

The (SPD) arresters DEHNbloc® M and DEHNgap M are coordinated directly with SPD type 2. Maximum continuous voltage (UC) Standard IEC 61643-11 specifies that the maximum continuous voltage of a SPD is the maximum value of the effective or constant voltage that can be applied permanently to the SPD.

According with the standard IEC CLC / TS 61643-12, this parameter must be sized according to:

- Installation mode (phase-neutral or phase-to-ground);

- Form of B.T. network (TT, TN or IT);

- Voltage network between phase and neutral (U0).

The dimensioning of the U SPD must be performed as follows:

- installed in TT and TN network phase-to-neutral or phase-to-ground:

- installed in an IT network phase-to-neutral: UC ≥ 1.1 x U0

- installed in a IT network phase-to-ground: UC ≥ 1,732 x U0

- installed in a TT, TN and IT network neutral-to-ground: UC ≥ U0

This dimensioning applies only to the SPD in conformity with IEC EN 61643-11 standard, because it involves the "Proof of failure to TOV" (temporary overvoltage). With this test an AC mains voltage to the SPD terminal is applied. The SPD has passed the tests, when:

- It does not get damaged;

- It damaged, but it does not create a hazardous situation (ie does not catch fire or uncovers any part under voltage).

The SPD of DEHN fully meet the requirements of the product standard CEI EN 61643-11, in reference to the TOV tests.

Reviews

Recensioni

Write a review

DEHN GUARD SURGE ARRESTER DG M TT 2P 275 - A.C. SINGLE PHASE - 952110

DEHN GUARD SURGE ARRESTER DG M TT 2P 275 - A.C. SINGLE PHASE - 952110

DEHN GUARD DG M TT 2P 275 surge arrester - A.C. SINGLE PHASE - 952110, lightning current arrester, coordinated SPD Type 1

Write a review

5 other products in the same category:

Avaliable in stores:

Fly solartech solutions srl
Piazza Carlo Cattaneo 6 33038

33038 San Dan, Udine
Italia
Phone: 0432 955377 Get Directions

Download